Introducing ANTSPACE HW5 I: The Ultimate Mining Solution
The ANTSPACE HW5, a powerful and efficient mining solution with a 1200 kW power capacity. Designed as a Dry-Wet Tower, this state-of-the-art unit supports up to 210 miners, making it a robust choice for high-demand mining operations. The all-in-one design of the ANTSPACE HW5 I is not only time-saving but also space and money-saving, providing significant advantages for large-scale deployments. Encased in a brand new 40-feet container, this solution combines efficiency and convenience, setting a new standard in the mining industry.


Bitmain Antspace HW5 1200KW Dry-Wet Tower
✓ Product: ANTSPACE HW5
✓ Power Capacity: 1200 kW
✓ Tower Type: Dry-Wet Tower
✓ Miner Capacity: 210 MINER CAPACITY
✓ Design: All In One
✓ Benefits: Time, Space, and Money Saving
✓ Feature: Brand new 40-feet container
NOTES:
1. The ANTSPACE HW5 is recommended to be used simultaneously with The ANTMINER S19 Hyd. / S21 Hyd. Series miner.
2. The pictures shown are for reference only; the final shipment version shall prevail.
Specifications Details for ANTSPACE HW5 in the tables below:
| Product Glance |
Value |
| Model | ANTSPACE HW5 |
| Version | V1 |
| Dimensions (l*w*h) (mm) | 12192×2438×2896 |
| Miner capacity | 210 units -S19 Hyd. &S21 Hyd. Series miner |
| Container certification | China Classification Society Certification |
| Safety certification | NFPA 79:2021
UL 508A:2018 R8.21 CSA C22.2 No. 14-18 ANSI/ISO 12100:2012 IEC 60204 Ed 5.1 2009 |
| Operating power(kW) | 1062 |
| PUE(Power usage effectiveness) | 1.032 |
| Input voltage and frequency | 400V±5% 50/60Hz |
| Detailed Characteristics | |
| Shipping weight(T) | 14 |
| Operating weight (T) | 24 |
| Main switch of power distribution cabinets(A) | 1200*2 |
| Rated current(A) | ≤986 |
| Rated Current per Miner (A) | ≤10 |
| Inlet cable | The inlet cables can withstand high-voltage of above 600V, with the following requirements:
L1 single core cable 600kcMil(300mm²)x4 L2 single core cable 600kcMil(300mm²)x4 L3 single core cable 600kcMil(300mm²)x4 N Single-core cable 600kcMil(300mm²)x4 PE single-core cable 500kcMil(240mm²)x2 |
| Flow rate(m³/h) | ≥85 |
| Quantity of ANTSPACE powered by one 2500kVA Transformer | 2 |
| Dry-Wet Tower | |
| Heat Dissipation Capacity (kW) | 1200 kW |
| Outlet Temperature @ 28℃ Wet Bulb Temperature | 35℃ |
| Container Certification | China Classification Society Certification |
| Operating Power (kW) | 15~29 |
| Motor Rated Voltage and Frequency | 400V±5% 50/60Hz |
| Motor Rated Voltage and Frequency | DN40(Internal thread) |
| Drain Pipe Interface | DN65(Internal thread) |
| Noise Level @25℃, 15m | 70 dBA |
| Water Consumption (m³/h) | 0.7~1.3m³/h |
Points For Attention
| 1 | The cooling tower must be placed on a flat ground with a level of ±1 degree. |
| 2 | The surface ground needs to be hardened and aimed to hold the ANTSPACE to be stable to withstand the load of at least 36 tons. |
| 3 | The customers need to prepare a 20-ton crane to load and unload ANTSPACE and Cooling-tower. |
| 4 | Stairs, walkway boards, transformers, cables, bridges, cable distribution boxes, and other external facilities are not included in ANTSPACE products. |
| 5 | If you plan to store ANTSPACE units vertically on top of one another, please advise the BITMAIN sales team regarding the preferred opening direction for the door facing the air inlet of your ANTSAPCE unit. The door opens to the left by default. |
| 6 | Leave at least 2 meters of air inlet space around the cooling tower. |
| 7 | Operating elevation: lower than 2000 meters. If the height is more significant than 1000 meters and a 2500kVA transformer, the number of ANTSAPCE units installed in one ANTSPACE unit must be decreased by around 1%. |
| 8 | Environmental requirements: Temperature: -25°C~40°C; Humidity 10%RH~90%RH; The ambient temperature requirement in high-humidity areas is not higher than 40°C. When the ambient temperature is lower than 0°C, the inlet and outlet shutters need to be closed, and the interior of the mining machine can only be started when it is heated to above 20°C. |
| 9 | The ambient temperature of the ANTSPACE does not represent the ambient temperature of the mining machine. |
Download
Only logged in customers who have purchased this product may leave a review.








Reviews
There are no reviews yet.